Найти
Телефон
Меню

Официальный представитель завода АО «Таурас-Феникс»

в Уфе, в Казани, в Оренбурге, в Перми, в Ижевске и в Казахстане

Taures-fenix
+7 347 201 77 10 Бесплатно по России

PI1612 – фото
PI1612 – фото
PI1612 – фото
PI1612 – фото
Фото
Видео

На PI1612

Для заявки пишите в МАХ или Telegram

# #

Характеристики

Output signal switching signal; analog signal; IO-Link
Measuring range 0...160
Medium temperature -25...150
Electrical design PNP/NPN
Process connection G 1 external thread sealing cone

Все характеристики

Number of inputs and outputs Number of digital outputs: 2; Number of analog outputs: 1
Measuring range
0...160 bar0...2320 psi0...16 MPa
Process connection threaded connection G 1 external thread sealing cone
System gold-plated contacts
Application flush mountable for the food and beverage industry
Media viscous media and liquids with suspended particles; liquids and gases; use in gases at pressures > 25 bar only on request
Medium temperature -25...150
Min. bursting pressure
650 bar9425 psi65 MPa
Pressure rating
200 bar2900 psi20 MPa
Vacuum resistance
-1000 mbar-0.1 MPa
Type of pressure relative pressure; vacuum
No dead space yes
Min. insulation resistance 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Integrated watchdog yes
Step response time analog output 30
Min. response time of switching output (dAP) 3
Step response time analog output 7
Number of inputs and outputs Number of digital outputs: 2; Number of analog outputs: 1
Total number of outputs 2
Output signal switching signal; analog signal; IO-Link
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / closed; (configurable)
Number of analog outputs 1
Analog current output 4...20, invertible; (scalable)
Short-circuit protection yes
Type of short-circuit protection yes (non-latching)
Overload protection yes
Measuring range
0...160 bar0...2320 psi0...16 MPa
Set point SP
0.2...160 bar3...2321 psi0.02...16 MPa
Reset point rP
0...159.8 bar0...2317 psi0...15.98 MPa
Analog start point
0...128 bar0...1856 psi0...12.8 MPa
Analog end point
32...160 bar464...2321 psi3.2...16 MPa
Min. difference between SP and rP
0.2 bar3 psi0.02 MPa
In steps of
0.1 bar1 psi0.01 MPa
Factory setting
SP1 = 40 barrP1 = 36.8 bar
SP2 = 120 barrP2 = 116.8 bar
ASP = 0.00 barAEP = 160 bar
dAP = 0.06 sdAA = 0.06 s
Accuracy ± 2,5+ (0,08 x ( Umgebungstemperatur - Mediumtemperatur ))
Repeatability ± 0,2
Resolution 0.2
Switch point accuracy < ± 0,5; (DIN EN IEC 62828-1; Turn down 1:1)
Repeatability < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation < ± 0,5; (DIN IEC EN 62828-1 incl. zero point and span error, non-linearity, hysteresis; Turn down 1:1)
Linearity deviation < ± 0,15; (Turn down 1:1)
Zero-point stabilization
IO-Link, analog output0,15; (see operating instructions zero-point behavior)
Display, Switching output0,2
Hysteresis deviation < ± 0,15; (Turn down 1:1)
Long-term stability < ± 0,1; (Turn down 1:1; per year)
Total deviation over temperature range
Temperature rangetotal deviation
-25...15 °CCharacteristics deviation ± 0,15 % of the span / 10 K
15...80 °CCharacteristics deviation
80...150 °CCharacteristics deviation ± 0,2 % of the span / 10 K
Notes on the accuracy / deviation for further details see section Diagrams and graphs
Damping process value dAP 0...99.99
Damping for the analog output dAA 0...99.99
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
Profiles
Common - I&DIdentification and Diagnosis
FunctionMeasurement data, high resolution
SIO mode yes
Required master port class A
Min. process cycle time 5.6
IO-Link resolution pressure 0.005
IO-Link resolution temperature 0.2
IO-Link process data (cyclical)
Functionbit length
pressure32
temperature32
device status4
binary switching information2
IO-Link functions (acyclical) application specific tag; internal temperature; operating hours counter; switching cycles counter; Pressure peak counter; measuring cell diagnosis
Supported DeviceIDs
Type of operationDeviceID
default1825
Ambient temperature -25...80
Storage temperature -40...100
Protection IP 67; IP 68; IP 69K
EMC
DIN EN 61326-1
Shock resistance
DIN EN 60068-2-2750 g (11 ms)
Vibration resistance
DIN EN 60068-2-620 g (10...2000 Hz)
MTTF 201
UL approval
UL approval numberJ034
File number ULE174189
Weight 399.6
Housing tubular
Dimensions Ø 50 / L = 116
Material Housing: stainless steel (1.4404 / 316L); Pushbuttons: PBT; sealings: FKM; M12 connector: PEI; Display: PFA
Materials (wetted parts) measuring cell: ceramics (99.9 % Al2O3); Process connection: stainless steel (1.4435 / 316L) surface characteristics: Ra < 0,4 µm / Rz = 4 µm; sealing: PTFE
Min. pressure cycles 100 million
Tightening torque 20
Process connection threaded connection G 1 external thread sealing cone
Display
Display unitLED, green
Switching statusLED, yellow
Function displayalphanumeric display, 4-digit
Measured valuesalphanumeric display, 4-digit
Display unit bar; psi; MPa
Pack quantity 1 pcs.
Connection Connector: 1 x M12; coding: A; Contacts: gold-plated