Характеристики

Sensing range 10 mm non-flush mountable
Output AC/DC
Dimensions Ø 20 / L = 92
Switching frequency 25 Hz AC / 70 Hz DC
Output function normally open / closed; (selectable)

Все характеристики

Output function normally open / closed; (selectable)
Sensing range 10
Housing tubular
Dimensions Ø 20 / L = 92
Operating voltage 20...250 AC/DC
Protection class II
Reverse polarity protection no
Output function normally open / closed; (selectable)
Max. voltage drop switching output DC 6
Max. voltage drop switching output AC 6.5
Minimum load current 5
Max. leakage current 2.5 (250 V AC) / 1.3 (110 V AC) / 0.8 (24 V DC)
Permanent current rating of switching output AC 250; (350 (...50 °C))
Permanent current rating of switching output DC 100
Short-time current rating of switching output 2200; (20 ms / 0,5 Hz)
Switching frequency AC 25
Switching frequency DC 70
Short-circuit proof no
Overload protection no
Sensing range 10
Real sensing range Sr 10 ± 10 %
Operating distance 0...8.1
Correction factor steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminum: 0.3 / copper: 0.2
Hysteresis 1...15
Switch-point drift -10...10
Ambient temperature -25...80
Protection IP 65
EMC
EN 60947-5-2
EN 55011class B
MTTF 606
UL approval
Ta0...40 °C
Enclosure typeType 1
File number ULE174191
Weight 83.5
Housing tubular
Mounting non-flush mountable
Dimensions Ø 20 / L = 92
Material PBT; LED window: PC
Display
Switching status1 x LED, yellow
Connection terminals: ...2.5 mm²; Cable sheath: Ø 4.5...10 mm; Cable gland: M16 X 1.5
Items supplied
Mounting clamp: 1
Remarks
Recommendation: check the unit for reliable function after a short circuit.
Pack quantity 1 pcs.

Приемущества

With combined AC/DC output stage
Two-wire technology
Smooth plastic housing to protect against deposits
With terminal chamber that can be rotated by 90°
High protection rating for the requirements of harsh industrial environments