| Output function |
normally closed |
| Sensing range |
8 |
| Housing |
Threaded type |
| Dimensions |
M18 x 1 / L = 84 |
| Operating voltage |
20...250 AC/DC |
| Protection class |
II |
| Reverse polarity protection |
no |
| Output function |
normally closed |
| Max. voltage drop switching output DC |
6 |
| Max. voltage drop switching output AC |
6 |
| Minimum load current |
4 |
| Max. leakage current |
2.5 (250 V AC) / 1.7 (110 V AC) / 1.5 (24 V DC) |
| Permanent current rating of switching output AC |
150; (350 (...50 °C)) |
| Permanent current rating of switching output DC |
100 |
| Short-time current rating of switching output |
2100; (20 ms / 0,5 Hz) |
| Switching frequency AC |
25 |
| Switching frequency DC |
50 |
| Short-circuit proof |
no |
| Overload protection |
no |
| Sensing range |
8 |
| Real sensing range Sr |
8 ± 10 % |
| Operating distance |
0...6.5 |
| Correction factor |
glass: 0.4 / water: 1 / ceramics: 0.2 / PVC: 0.2 |
| Hysteresis |
1...15 |
| Switch-point drift |
-15...15 |
| Ambient temperature |
-25...80 |
| Protection |
IP 67 |
| EMC |
|
| MTTF |
334 |
| Weight |
89.5 |
| Housing |
Threaded type |
| Mounting |
non-flush mountable |
| Dimensions |
M18 x 1 / L = 84 |
| Thread designation |
M18 x 1 |
| Material |
PBT |
| Display |
| Switching status | 1 x LED, yellow |
|
| Connection |
Cable: 2 m, PVC; 2 x 0.34 mm² |
| Items supplied |
|
| Remarks |
| Recommendation: check the unit for reliable function after a short circuit. |
|
| Pack quantity |
1 pcs. |