Найти
Телефон
Меню

Официальный представитель завода АО «Таурас-Феникс»

в Уфе, в Казани, в Оренбурге, в Перми, в Ижевске и в Казахстане

Taures-fenix
+7 347 201 77 10 Бесплатно по России

PV8002 – фото
PV8002 – фото
PV8002 – фото
Фото
Видео

На PV8002

Для заявки пишите в МАХ или Telegram

# #

Характеристики

Output signal switching signal; IO-Link; (configurable)
Measuring range 0...100
Medium temperature -40...90
Electrical design PNP/NPN
Process connection G 1/4 external thread

Все характеристики

Product characteristics
Number of inputs and outputs Number of digital outputs: 2
Measuring range <table><tr><td>0...100 bar</td><td>0...1450 psi</td><td>0...10 MPa</td></tr></table>
Process connection threaded connection G 1/4 external thread (DIN EN ISO 1179-2); Internal thread:M5
Application
Measuring element metallic thin film cell
Application for industrial applications
Media liquids and gases
Medium temperature -40...90
Min. bursting pressure <table><tr><td>1000 bar</td><td>14500 psi</td><td>100 MPa</td></tr></table>
Pressure rating <table><tr><td>250 bar</td><td>3625 psi</td><td>25 MPa</td></tr></table>
Note on pressure rating <table><tr><td>static </td></tr></table>
Vacuum resistance <table><tr><td>-1000 mbar</td><td>-0.1 MPa</td></tr></table>
Type of pressure relative pressure
Electrical data
Operating voltage 18...30 DC
Current consumption < 15
Min. insulation resistance 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time < 0.3
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2
Outputs
Total number of outputs 2
Output signal switching signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / closed; (configurable)
Max. voltage drop switching output DC 2
Permanent current rating of switching output DC 100
Switching frequency DC < 130
Short-circuit protection yes
Type of short-circuit protection yes (non-latching)
Overload protection yes
Measuring/setting range
Measuring range <table><tr><td>0...100 bar</td><td>0...1450 psi</td><td>0...10 MPa</td></tr></table>
Set point SP <table><tr><td>1...100 bar</td><td>15...1450 psi</td><td>0.1...10 MPa</td></tr></table>
Reset point rP <table><tr><td>0.51...99.51 bar</td><td>7...1443 psi</td><td>0.051...9.951 MPa</td></tr></table>
In steps of <table><tr><td>0.01 bar</td><td>1 psi</td><td>0.001 MPa</td></tr></table>
Factory setting <table><tr><td>SP1 = 25 bar</td><td>rP1 = 23 bar</td><td>ou1 = Hno;</td></tr><tr><td>SP2 = 75 bar</td><td>rP2 = 73 bar</td><td>ou2 = Hno;</td></tr><tr><td>dS1/dS2 = 0 ms</td><td>dr1/dr2 = 0 ms</td><td></td></tr><tr><td>coF = 0 %</td><td>P-n = PnP</td><td>
Temperature monitoring
Accuracy ± 2 K + (0.1 x (ambient temperature - medium temperature))
Notes on the accuracy / deviation temperature range -10 to 80 °C
Accuracy / deviations
Switch point accuracy < ± 0,5 (nach DIN EN 61298-2)
Repeatability < ± 0,05; (with temperature fluctuations < 10 K)
Characteristics deviation < ± 0,5; (linearity incl. hysteresis and repeatability, limit value setting to DIN EN IEC 62828-1)
Linearity deviation < ± 0,1 (BFSL) / < ± 0,2 (LS)
Hysteresis deviation < ± 0,2
Long-term stability < ± 0,1; (per 6 months)
Temperature coefficient zero point < 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C)
Temperature coefficient span < 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C)
Reaction times
Response time < 3
Software / programming
Parameter setting options hysteresis / window; normally open / closed; switching logic; switch-on/switch-off delay; Damping
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
Profiles <table><tr><td>Common - I&D</td><td>Identification and Diagnosis</td></tr><tr><td>Function</td><td>Measurement data, standard resolution</td></tr></table>
SIO mode yes
Required master port class A
Process data analog 5
Process data binary 2
Min. process cycle time 4.5
IO-Link resolution pressure 0.05
IO-Link resolution temperature 0.2
IO-Link process data (cyclical) <table><tr><th>Function</th><th>bit length</th></tr><tr><td>pressure</td><td>16</td></tr><tr><td>temperature</td><td>16</td></tr><tr><td>device status</td><td>4</td></tr><tr><td>binary switching information</td><td>2</td></tr></table>
IO-Link functions (acyclical) application specific tag; internal temperature; operating hours counter; switching cycles counter; Pressure peak counter; Temperature peak counter
Supported DeviceIDs <table><tr><th>Type of operation</th><th>DeviceID</th></tr><tr><td>default</td><td>1212</td></tr></table>
Operating conditions
Ambient temperature -40...90
Storage temperature -40...100
Protection IP 67; IP 69K
Tests / approvals
EMC <table><tr><td>DIN EN 61326-1</td><td></td></tr></table>
Shock resistance <table><tr><td>DIN EN 60068-2-27</td><td>500 g (1 ms)</td></tr></table>
Vibration resistance <table><tr><td>DIN EN 60068-2-6</td><td>20 g (10...2000 Hz)</td></tr></table>
MTTF 668
UL approval <table><tr><td>UL approval number</td><td>J038 </td></tr><tr><td>File number UL</td><td>E174189 </td></tr></table>
Pressure equipment directive sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight 56.8
Housing tubular
Dimensions Ø 19 / L = 66
Material stainless steel (630/1.4542/17-4 PH); stainless steel (1.4404 / 316L); PEI
Materials (wetted parts) stainless steel (1.4305 / 303); stainless steel (630/1.4542/17-4 PH)
Min. pressure cycles 60 million; (at 1.2 times nominal pressure)
Tightening torque 25...35; (recommended tightening torque; Depends on lubrication, seal and pressure rating)
Process connection threaded connection G 1/4 external thread (DIN EN ISO 1179-2); Internal thread:M5
Process connection sealing FKM (DIN EN ISO 1179-2)
Restrictor element integrated yes
Remarks
Remarks <table><tr><td>BFSL = Best Fit Straight Line</td></tr><tr><td>LS = limit value setting</td></tr></table>
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A

Приемущества

Compact housing for use where space is restricted
Very high overpressure and vacuum resistance
Robust stainless steel housing with high shock and vibration resistance
Two programmable switching outputs, one of them with IO-Link communication interface
Integrated temperature measurement via IO-Link
User-friendly communication and parameterization via IO-Link