| Product characteristics |
|
| Number of inputs and outputs |
Number of digital outputs: 2 |
| Measuring range |
<table><tr><td>0...25 bar</td><td>0...363 psi</td><td>0...2.5 MPa</td></tr></table> |
| Process connection |
threaded connection G 1/4 external thread Internal thread:M5 |
| Application |
|
| Application |
for industrial applications |
| Media |
liquids and gases |
| Medium temperature |
-25...90 |
| Min. bursting pressure |
<table><tr><td>350 bar</td><td>5075 psi</td><td>35 MPa</td></tr></table> |
| Pressure rating |
<table><tr><td>150 bar</td><td>2175 psi</td><td>15 MPa</td></tr></table> |
| Type of pressure |
relative pressure |
| Electrical data |
|
| Operating voltage |
9.6...36 DC; (communication mode: 18...32) |
| Current consumption |
< 45 |
| Min. insulation resistance |
100; (500 V DC) |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time |
0.3 |
| Inputs / outputs |
|
| Number of inputs and outputs |
Number of digital outputs: 2 |
| Outputs |
|
| Total number of outputs |
2 |
| Output signal |
switching signal; IO-Link; (configurable) |
| Electrical design |
PNP |
| Number of digital outputs |
2 |
| Output function |
normally open / closed; (configurable) |
| Max. voltage drop switching output DC |
2 |
| Permanent current rating of switching output DC |
250 |
| Switching frequency DC |
170 |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
yes (non-latching) |
| Overload protection |
yes |
| Measuring/setting range |
|
| Measuring range |
<table><tr><td>0...25 bar</td><td>0...363 psi</td><td>0...2.5 MPa</td></tr></table> |
| Set point SP |
<table><tr><td>0.2...25 bar</td><td>4...362 psi</td><td>0.02...2.5 MPa</td></tr></table> |
| Reset point rP |
<table><tr><td>0.1...24.9 bar</td><td>2...360 psi</td><td>0.01...2.49 MPa</td></tr></table> |
| In steps of |
<table><tr><td>0.1 bar</td><td>2 psi</td><td>0.01 MPa</td></tr></table> |
| Factory setting |
<table><tr><td></td><td>SP1 = 6.3 bar</td><td>rP1 = 5.8 bar</td></tr><tr><td></td><td>SP2 = 18.8 bar</td><td>rP2 = 18.3 bar</td></tr><tr><td></td><td>OUT1 = Hno</td><td>OUT2 = Hno</td></tr></table> |
| Accuracy / deviations |
|
| Switch point accuracy |
< ± 0,5 |
| Repeatability |
< ± 0,1; (with temperature fluctuations < 10 K) |
| Characteristics deviation |
< ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
| Hysteresis deviation |
< ± 0,1 |
| Long-term stability |
< ± 0,1; (per year) |
| Temperature coefficient zero point |
< ± 0,2; (0...80 °C) |
| Temperature coefficient span |
< ± 0,2; (0...80 °C) |
| Reaction times |
|
| Response time |
< 3 |
| Damping process value dAP in steps |
0,003 - 0,006 - 0,010 - 0,017 - 0,060 - 0,125 - 0,250 - 0,500 |
| Interfaces |
|
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.0 |
| SIO mode |
yes |
| Required master port class |
A |
| Process data analog |
1 |
| Process data binary |
2 |
| Min. process cycle time |
2.3 |
| Supported DeviceIDs |
<table><tr><th>Type of operation</th><th>DeviceID</th></tr><tr><td>default</td><td>5</td></tr></table> |
| Operating conditions |
|
| Ambient temperature |
-25...85 |
| Storage temperature |
-40...100 |
| Protection |
IP 68; (7 days / 1 m water depth / 0.1 bar) |
| Tests / approvals |
|
| EMC |
<table><tr><td>noise immunity</td><td>EN 61000-6-2</td></tr><tr><td>EN 61000-4-2 ESD</td><td>4 kV contact discharge / 15 kV air discharge</td></tr><tr><td>EN 61000-4-3 HF radiated</td><td>20 V/m</td></tr><tr><td>EN 61000-4-4 Burst</td><td>4 kV coupling cl |
| Shock resistance |
<table><tr><td>DIN IEC 60068-2-27 / DIN IEC 60068-2-29</td><td>1000 g</td></tr><tr><td>DIN EN 61373</td><td>Category 3</td></tr></table> |
| Vibration resistance |
<table><tr><td>DIN IEC 68-2-6</td><td>20 g (10...2000 Hz)</td></tr><tr><td>DIN EN 60068-2-64</td><td>14 g</td></tr><tr><td>DIN EN 61373</td><td>Category 2</td></tr></table> |
| MTTF |
310 |
| Pressure equipment directive |
sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Mechanical data |
|
| Weight |
226.5 |
| Housing |
tubular |
| Dimensions |
Ø 30 / L = 79.5 |
| Material |
stainless steel (1.4301 / 304); FKM; EPDM/X; PA |
| Materials (wetted parts) |
stainless steel (1.4305 / 303); ceramics; FKM |
| Min. pressure cycles |
100 million |
| Process connection |
threaded connection G 1/4 external thread Internal thread:M5 |
| Restrictor element integrated |
no (can be retrofitted) |
| Displays / operating elements |
|
| Display |
<table><tr><td>Power</td><td>2 x LED, green</td></tr><tr><td>Switching status</td><td>2 x LED, yellow</td></tr></table> |
| Teach function |
yes |
| Remarks |
|
| Remarks |
<table><tr><td> referring to UL: “limited voltage” with overcurrent protection in accordance with UL508</td></tr></table> |
| Pack quantity |
1 pcs. |
| Electrical connection |
|
| Connection |
Connector: 1 x M12; coding: A |