Найти
Телефон
Меню

Официальный представитель завода АО «Таурас-Феникс»

в Уфе, в Казани, в Оренбурге, в Перми, в Ижевске и в Казахстане

Taures-fenix
+7 347 201 77 10 Бесплатно по России

PS4208 – фото
Фото
Видео

На PS4208

Для заявки пишите в МАХ или Telegram

# #

Характеристики

Cable material FEP
Approval CE, UKCA
Measuring range 0...100.4
Cable length 5

Все характеристики

Number of inputs and outputs Number of analog outputs: 1
Measuring range
0...0.25 bar0...250 mbar0...3.63 psi0...100.4 inH2O0...25 kPa
Design with capillary tube for pressure compensation
Application for industrial applications
Media Liquids
Medium temperature -10...85
Min. bursting pressure
2.4 bar35 psi240 kPa
Pressure rating
2 bar29 psi200 kPa
Type of pressure relative pressure
Operating voltage 10...30 DC
Protection class III
Reverse polarity protection yes
Number of inputs and outputs Number of analog outputs: 1
Total number of outputs 1
Output signal analog signal
Number of analog outputs 1
Analog current output 4...20
Max. load 700; (Ub = 24 V; (Ub - 10 V) / 20 mA)
Short-circuit protection yes
Measuring range
0...0.25 bar0...250 mbar0...3.63 psi0...100.4 inH2O0...25 kPa
Repeatability < 0,1; (with temperature fluctuations < 10 K)
Characteristics deviation < 0,25 (BFSL) / 0,5; (incl. linearity, zero and span error (limit value setting))
Linearity deviation < 0,2 (BFSL)
Long-term stability < 0,2; (per year)
Temperature coefficient zero point < ± 0,2; (0...50 °C)
Temperature coefficient span < ± 0,2; (0...50 °C)
Ambient temperature -10...85
Storage temperature -30...80
Protection IP 68
MTTF 403
Pressure equipment directive sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight 650.6
Housing tubular
Dimensions Ø 27 / L = 147
Material stainless steel (1.4571/316Ti ); PA
Pack quantity 1 pcs.
Connection Cable: 5 m, FEP, Ø 7.5 mm

Приемущества

Low-cost, simple level measurement
Pressure compensation via internally vented cable
Reduced wiring complexity when operated as two-wire current loop
High overall accuracy and long-term stability
Robust stainless steel housing with high ingress resistance