Характеристики

Output signal analog signal
Medium temperature -25...90
Measuring range 0...103
Process connection 1/4" NPT external thread

Все характеристики

Number of inputs and outputs Number of analog outputs: 1
Measuring range
0...15 psi0...103 kPa
Process connection threaded connection 1/4" NPT external thread Internal thread:M5
System gold-plated contacts
Application for industrial applications
Media liquids and gases
Medium temperature -25...90
Min. bursting pressure
450 psi3.1 MPa
Pressure rating
145 psi1 MPa
Type of pressure relative pressure
Operating voltage 16...32 DC
Current consumption < 18
Min. insulation resistance 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Number of inputs and outputs Number of analog outputs: 1
Total number of outputs 1
Output signal analog signal
Number of analog outputs 1
Analog voltage output 0...10
Min. load resistance 2000
Overload protection yes
Measuring range
0...15 psi0...103 kPa
Repeatability < 0,1; (with temperature fluctuations < 10 K)
Characteristics deviation < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Long-term stability < ± 0,05; (per 6 months)
Temperature coefficient zero point 0,15; (0...80 °C)
Temperature coefficient span 0,2; (0...80 °C)
Step response time analog output 3
Ambient temperature -25...80
Storage temperature -40...100
Protection IP 65
EMC
EN 61000-4-2 ESD4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated30 V/m
EN 61000-4-4 Burst2 kV
EN 61000-4-6 HF conducted10 V
radiation of interferenceaccording to the automotive directive 2004/104/EC / CISPR 25
noise immunityaccording to the automotive directive 2004/104/EC / ISO 11452-2
HF radiated100 V/m
pulse resistanceISO 7637-2 / severity level 3
Shock resistance
DIN IEC 68-2-2750 g (11 ms)
Vibration resistance
DIN IEC 68-2-620 g (10...2000 Hz)
MTTF 550
Pressure equipment directive sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight 211.5
Housing tubular
Dimensions Ø 30 / L = 79.5
Material stainless steel (1.4404 / 316L); FKM; PA; EPDM/X
Materials (wetted parts) stainless steel (1.4305 / 303); ceramics; FKM
Min. pressure cycles 100 million
Process connection threaded connection 1/4" NPT external thread Internal thread:M5
Restrictor element integrated no (can be retrofitted)
Pack quantity 1 pcs.
Connection Connector: 1 x M12; coding: A; Contacts: gold-plated

Приемущества

Reliable detection of system pressure in industrial and mobile applications
Precise analog output
With long-term stability thanks to high overload protection
Lifespan of more than 100 million pressure cycles
High shock and vibration resistance