Найти
Телефон
Меню

Официальный представитель завода АО «Таурас-Феникс»

в Уфе, в Казани, в Оренбурге, в Перми, в Ижевске и в Казахстане

Taures-fenix
+7 347 201 77 10 Бесплатно по России

O1D300 – фото
O1D300 – фото
O1D300 – фото
O1D300 – фото
Фото
Видео

На O1D300

Для заявки пишите в МАХ или Telegram

# #

Характеристики

Output function normally open / closed; (programmable); analog
Laser protection class 2
Dimensions 59 x 42 x 52
Product designation Optical level sensor
Measuring range 0.2...10

Все характеристики

Product characteristics
Laser protection class 2
Housing rectangular
Electrical data
Operating voltage 18...30 DC; (cULus - Class 2 source required)
Current consumption < 150
Protection class III
Reverse polarity protection yes
Typ. lifetime 50000
Measuring principle photoelectric
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analog outputs: 1
Outputs
Total number of outputs 2
Electrical design PNP
Number of digital outputs 2
Output function normally open / closed; (programmable)
Max. current load per output 200
Number of analog outputs 1
Analog current output 4...20; (IEC 61131-2)
Max. load 250
Analog voltage output 0...10; (IEC 61131-2)
Min. load resistance 5000
Short-circuit protection yes
Type of short-circuit protection yes (non-latching)
Overload protection yes
Monitoring range
Max. light spot width 15
Max. light spot height 15
Light spot dimensions refer to 10 m
Background suppression 10...100
Measuring/setting range
Measuring range 0.2...10; (white paper 200 x 200 mm 90 % remission)
Sampling rate 1...33
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
Profiles <table><tr><td>Smart Sensor - SSP 0</td><td>Generic Profiled Sensor</td></tr><tr><td>Function</td><td>Device identification</td></tr><tr><td>Function</td><td>Process data variable</td></tr><tr><td>Function</td><td>Device diagnosis</td></tr></table>
SIO mode yes
Required master port class A
Process data analog 2
Process data binary 2
Min. process cycle time 5
Supported DeviceIDs <table><tr><th>Type of operation</th><th>DeviceID</th></tr><tr><td>default</td><td>813</td></tr></table>
Operating conditions
Ambient temperature -10...60
Protection IP 67
Tests / approvals
EMC <table><tr><td>EN 60947-5-2</td><td></td></tr></table>
Laser protection class 2
Notes on laser protection <table><tr><td>Caution:</td><td>Laser light</td></tr><tr><td>Power:</td><td><= 4,0 mW</td></tr><tr><td>Wave length:</td><td>650 nm</td></tr><tr><td>pulse:</td><td>1,3 ns</td></tr><tr><td>Do not stare into beam.</td><td></td></tr><tr><td>Avoid exposure to
MTTF 107
Mechanical data
Weight 240
Housing rectangular
Dimensions 59 x 42 x 52
Material housing: diecast zinc; front lens: glass; LED window: PC
Lens alignment Side sensing
Displays / operating elements
Display <table><tr><td>Switching status</td><td>2 x LED, yellow</td></tr><tr><td>Power</td><td>LED, green</td></tr><tr><td>Distance, programming</td><td>alphanumeric display, 4-digit</td></tr></table>
Accessories
Accessories (optional) <table><tr><td>Protective cover, E21133</td></tr></table>
Remarks
Remarks <table><tr><td> cULus - Class 2 source required</td></tr></table>
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A

Приемущества

Reliable optical level measurement with high ranges up to 9.8 m
Scalable measuring range and window function
Two switching outputs, one of them programmable as analog output
Wide range of components for quick mounting and precise fine adjustment
Excellent price/performance ratio
User-friendly communication and parameterization via IO-Link