Характеристики

Output function analog
Materials (wetted parts) sensor: PPSU; Pipe section: PPS 40% glass fiber; sealing: EPDM
Measuring range 0.133...2.21
Process connection G 1/2 external thread DN8

Все характеристики

Product characteristics
Number of inputs and outputs Number of analog outputs: 1
Measuring range <table><tr><td>0.9...15 l/min</td><td>0.133...2.21 m/s</td></tr></table>
Process connection threaded connection G 1/2 external thread DN8
Application
System gold-plated contacts
Measuring element 1 x Pt 1000; (to DIN EN 60751, class B)
Application for industrial applications
Installation connection to pipe by means of an adapter
Media ultra-pure water; water; glycol solutions; Coolants
Medium temperature -15...125
Min. bursting pressure <table><tr><td>25 bar</td><td>2.5 MPa</td></tr></table>
Note on min. burst pressure <table><tr><td> 125 °C</td></tr></table>
Pressure rating <table><tr><td>16 bar</td><td>1.6 MPa</td></tr></table>
Note on pressure rating <table><tr><td>≤ 90 °C </td></tr></table>
Electrical data
Operating voltage 8...33 DC
Current consumption < 5
Min. insulation resistance 100; (500 V DC)
Protection class III
Power-on delay time < 2
Measuring principle Vortex
Inputs / outputs
Number of inputs and outputs Number of analog outputs: 1
Outputs
Total number of outputs 1
Output signal analog signal
Number of analog outputs 1
Analog current output 4...20
Max. load < (Ub - 8 V) / 20 mA; Ub = 24 V: 800
Measuring/setting range
Measuring range <table><tr><td>0.9...15 l/min</td><td>0.133...2.21 m/s</td></tr></table>
Temperature monitoring
Dynamic response T05 / T09 < 10 / < 30
Accuracy / deviations
Flow monitoring
Response time 0.34; (T09)
Reaction times
Operating conditions
Ambient temperature -15...85
Note on ambient temperature <table><tr><td>Medium temperature > 0 °C: -40...85</td></tr></table>
Storage temperature -40...85
Protection IP 65
Cavitation P(absolute) discharge / P(difference) > 5.5 to avoid cavitation
Tests / approvals
EMC <table><tr><td>EN IEC 61326-1:2021</td><td></td></tr></table>
Shock resistance <table><tr><td>DIN EN 60068-2-27</td><td>30 g (11 ms)</td></tr></table>
Vibration resistance <table><tr><td>DIN EN 60068-2-6</td><td>with water / 10...61 Hz 1 mm</td></tr><tr><td></td><td>with water / 61...2000 Hz 2 g</td></tr></table>
MTTF 395.9
Pressure equipment directive sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight 68.95
Housing rectangular
Dimensions 77 x 30.2 x 52.6
Material Housing: PPS 40% glass fiber; electronics: PC 10% glass fiber
Materials (wetted parts) sensor: PPSU; Pipe section: PPS 40% glass fiber; sealing: EPDM
Tightening torque 12
Process connection threaded connection G 1/2 external thread DN8
Remarks
Remarks <table><tr><td>MW = Measured value</td></tr><tr><td>MEW = Final value of the measuring range</td></tr></table>
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A; Contacts: gold-plated

Приемущества

Reliable detection of flow and medium temperature
Precise linearized analog output
Suitable for ultrapure water, water and water-based media
Durable and robust thanks to hydrolysis-resistant plastic
High precision of flow and temperature monitoring