Найти
Телефон
Меню

Официальный представитель завода АО «Таурас-Феникс»

в Уфе, в Казани, в Оренбурге, в Перми, в Ижевске и в Казахстане

Taures-fenix
+7 347 201 77 10 Бесплатно по России

AC509S – фото
AC509S – фото
AC509S – фото
Фото
Видео

На AC509S

Для заявки пишите в МАХ или Telegram

# #

Характеристики

Product designation AS-i input/output module

Все характеристики

Design housing for DIN rail mounting
Application AS-i Safety at Work
Operating voltage 26.5...31.6 DC; (cULus - Class 2 source required)
Current consumption < 280
Max. current load per module/slot 0.2
Integrated watchdog yes
Number of inputs and outputs Number of digital inputs: 4; Number of digital outputs: 2
Number of digital inputs 4; (2 x 2 safety inputs)
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Max. total current rating of inputs 200
Input current [mA]
8
Short-circuit detection
yes
Cross-fault monitoring
no
Short-circuit proof
yes
Output signal switching signal
Number of digital outputs 2
Voltage range DC 18...30; (AS-i)
Max. current load per output 50
Short-circuit proof yes
Electrically separated no
Actuator supply outputs AS-i
Ambient temperature -25...55
Note on ambient temperature
with switched outputs: -25...40 °C
Protection IP 67
EMC
EN 62026-2
EN 61326-3-1
Complies with the requirements
ISO 13849-1 Category 3, PL d
IEC 61508 SIL 2
MIssion time TM 175200
Mission time TM (additional indication)
20 years
PFH 2,33 E-11
AS-i version 2.11; 3.0
Extended addressing mode no
AS-i master profile M3; M4
AS-i profile S-7.B.E
AS-i I/O configuration 7
AS-i ID code B.E
AS-i certificate 128301
Weight 296.25
Housing rectangular
Type of mounting AS-i flat cable connection; Mounting on DIN rail; (TH35 (EN 60715))
Dimensions 103 x 45 x 44.7
Material housing: PA; Piercing contacts: CuSn6 nickel-plated and tin-plated
Display
Power1 x LED, green
errors1 x LED, red
Switching status1 x LED, yellow
alarm1 x LED, red
Module connection Flat cable
Items supplied
lower part
Accessories (optional)
Addressing cable:, E70213
Protective cap: M12, E73004
Remarks
PL d, cat. 3, SIL 2 only if the fault exclusions described in the manual are used
Pack quantity 1 pcs.
Connector: 2 x M12; coding: A; Maximum cable length: 10 m
Connector: 1 x M12; coding: A; Maximum cable length: 10 m
Connector: 1 x M12; coding: A; Maximum cable length: 10 m

Приемущества

Reliable detection of safety-related switching states
Integration of safety-related components in AS-i
Connection of safe mechanical and transistor inputs
Easy toolless installation
Clearly visible powerful LEDs for displaying operation, switching status and error