Найти
Телефон
Меню

Официальный представитель завода АО «Таурас-Феникс»

в Уфе, в Казани, в Оренбурге, в Перми, в Ижевске и в Казахстане

Taures-fenix
+7 347 201 77 10 Бесплатно по России

AC5275 – фото
Фото
Видео

На AC5275

Для заявки пишите в МАХ или Telegram

# #

Характеристики

Number of digital inputs 4
Number of digital outputs 4
Sensor supply of the inputs AS-i

Все характеристики

Application
Design housing for DIN rail mounting, Only for operation with AS-i masters with the profile M4
Application field installation
Electrical data
Operating voltage 26.5...31.6 DC; (cULus - Class 2 source required)
Max. current consumption from AS-i 250
Max. current load total 2
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 4; Number of digital outputs: 4
Inputs
Number of digital inputs 4
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Voltage supply 18...30; (via flat cable)
Max. total current rating of inputs 200
Input current High 6...10
Input current low 0...2
Switching level high > 11
Digital inputs protected against short circuits yes
Outputs
Number of digital outputs 4
Circuit PNP
Voltage range DC 15...30; (to PELV; via flat cable)
Max. current load per output 1000; (utilization category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1))
Short-circuit proof yes
Electrically separated yes
Actuator supply outputs AUX
Operating conditions
Ambient temperature -25...70
Protection IP 67
Tests / approvals
EMC <table><tr><td>EN 50295</td><td></td></tr><tr><td>IEC 61000-6-2</td><td></td></tr></table>
MTTF 155
AS-i classification
AS-i version 3.0
AS-i addressing Addressing socket
Extended addressing mode yes
AS-i master profile M4
AS-i profile S-7.A.7
AS-i I/O configuration 7
AS-i ID code A.7
Data bits <table><tr><td>Data bit</td><td>D0</td><td>D1</td><td>D2</td><td>D3</td></tr><tr><td>Input</td><td>1</td><td>2</td><td>3</td><td>4</td></tr><tr><td>Socket</td><td>I-1</td><td>I-2</td><td>I-3</td><td>I-4</td></tr><tr><td>Pin</td><td>4</td><td>4</td><td>4</
Mechanical data
Weight 291.5
Housing rectangular
Type of mounting quick mounting; AS-i flat cable connection; Mounting on DIN rail; (TH35 (EN 60715))
Dimensions 103 x 90 x 44.2
Material PA; Piercing contacts: CuSn6 nickel-plated and tin-plated
Displays / operating elements
Display <table><tr><td>Power</td><td>LED, green</td></tr><tr><td>errors</td><td>LED, red</td></tr><tr><td>Function</td><td>LED, yellow</td></tr></table>
Electrical connection
Accessories
Items supplied <table><tr><td>lower part</td></tr></table>
Accessories (optional) <table><tr><td>Protective cap: M12, E73004</td></tr></table>
Remarks
Remarks <table><tr><td> Inputs and outputs must be electrically isolated.</td></tr><tr><td> Do not connect any of the following points to an external potential:</td></tr><tr><td> I-, I+, I1, I2, I3, I4</td></tr><tr><td> The connections are electrically connected
Pack quantity 1 pcs.
Electrical connection - Inputs
Electrical connection - Outputs
Connection Connector: M12

Приемущества

Easy toolless installation
Three selectable directions of the flat cable mounting
Clearly visible powerful LEDs for displaying operation, switching status and error
High protection rating for the requirements of harsh industrial environments
Robust M12 connectors for connecting sensors and actuators