Характеристики

Number of digital inputs 4
Sensor supply of the inputs AS-i

Все характеристики

Design housing for DIN rail mounting
Application AS-i ATEX module
Operating voltage 26.5...31.6 DC
Max. current consumption from AS-i 250
Number of inputs and outputs Number of digital inputs: 4
Number of digital inputs 4
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Voltage supply 18...30; (via flat cable)
Max. total current rating of inputs 200
Input current High 6...10
Input current low 0...2
Switching level high > 11
Digital inputs protected against short circuits yes
Ambient temperature -10...50
Protection IP 50
ATEX marking II 3D Ex tc IIIB T80°C Dc X IP50
EMC
EN 50295
IEC 61000-6-2
MTTF 404
AS-i version 2.11; 3.0
AS-i addressing Addressing socket
Extended addressing mode no
AS-i master profile M2; M3; M4
AS-i profile S-0.0.E
AS-i I/O configuration 0
AS-i ID code 0.E
AS-i certificate pending yes
Data bits
Data bitD0D1D2D3
Input1234
SocketI-1I-2I-3I-4
Pin2+42+42+42+4
Weight 227.5
Housing rectangular
Type of mounting AS-i flat cable connection; Mounting on DIN rail; (TH35 (EN 60715))
Dimensions 103 x 45 x 44.7
Material PA; Piercing contacts: CuSn6 nickel-plated and tin-plated
Display
PowerLED, green
errorsLED, red
FunctionLED, yellow
Connector: 4 x M12; coding: A
Items supplied
lower part
Accessories (optional)
Protective cap: M12, E73004
impact protection housing:, E7000A
Remarks
Mechanical protection has to be implemented.
Otherwise the unit must be installed together with the impact protection housing (E7000A).
Do not connect any of the following points to an external potential:
I-, I+, I1, I2, I3, I4
The connections are electrically connected with the AS-i cable.
Pack quantity 1 pcs.

Приемущества

Easy toolless installation
Three selectable directions of the flat cable mounting
Clearly visible powerful LEDs for displaying operation, switching status and error
For applications in hazardous areas